Flameproof Temperature and Humidity Transmitter – Duct Mount – HTX-440-FLP-DM

Flameproof Temperature and Humidity Transmitter – Duct Mount – HTX-440-FLP-DM

Product Description :
HTX-440-FLP-DM – Flameproof Temperature and Humidity Transmitter – Duct Mount.

Libratherm offers low cost, rugged and reliable Flameproof Temperature and Humidity Transmitter – HTX-440-FLP-DM for sensing Temperature and RH simultaneously in the environment, whereas HX-440-FLP is for sensing only RH and transmitting the proportional analog value in the form of (4-20)mA or (0-10)VDC. The electronics part of the transmitter is housed in the FLP (Flameproof) head or junction box. so that it can be used in hazardous conditions.


Normally, the signal generated by T+RH sensors is low in strength hence cannot be transmitted over a very long distance, and if done so the signal is likely to drop over a very long cable which will result in the inaccurate measurement of Temperature and %RH.


The transmitter featured here converts these low-level signals from Pt-100 and RH sensor to the equivalent signal of 4-20mA/0-10VDC, which can be transmitted over a very long distance without loss of accuracy in the measurement.


These transmitters operate typically on a 24Vdc power supply (offers a wide range of 18 to 36VDC) and housed in an Aluminum die-casted flameproof head with a suitable length of SS extension pipe duly perforated for inserting the sensor in the Air duct area. The 24VDC supply and 4-20mA are electrically isolated from each other and hence prevent any ground line interferences or loading effect, while connecting to any external measuring/controlling devices like DCS, PLC, HMI or BMS controller DDC, PID, or On/Off controllers. A Standard 2-meter long cable with the end terminal is brought out from a suitable gland attached to the head for ease of connection and wiring.

Applications:
ItemT + RH sensor cum Transmitter / RH sensor cum Transmitter in FLP head or FLP junction box
Built in Sensors For Temp.: Pt-100 – Class A element (Hayashi-Denko Japan make)
For %Rh: Capacitive type Humidity sensor (Honeywell USA make)
Temp. Range 0 to 60oC (Std. range for HVAC applications)
Temp. Output (0-1) VDC / (4-20) mA / (0-10) VDC proportional to 0 to 60oC or proportional to selected temperature range.
RLmax = 400 Ohms for 4-20mA, RLmin = 100K for 0-10VDC
Temp. Accuracy± 0.5 oC
RH Range0 to 100%
%RH Output (0-1)VDC / (4-20) mA / (0-10)VDC proportional to 0 to 100%Rh
RLmax = 500 Ohms for (4-20)mA, RLmin = 100K for (0-10)VDC
RH Accuracy+/- 2% @ 25oC and 50% Rh
Isolation Voltage Greater than 1.5KV (4-20mA/0-10VDC Output and 24VDC Supply voltage are electrically isolated)
Supply Voltage24 VDC +/-10% @ 100mA max.
TypeDuct mounted in the Duct hole of 22 mm.
Enclosure / SS Stem Size FLP head or JB as per standard / 20mm Dia.x200mm (std. length)
Optional : Required non std. stem length can be provided on request.
Process Connection ½ inch BSP Thread below the head
Cable 4 core or 6 core PVC/PVC insulated 2meter long with standard colour code. Extra length of cable can be provided against order.
Precautions for useAvoid condensation and drench. Avoid exposure to saline, inorganic and organic gas.
Sr.No.ModelProduct DescriptionPart no.
1.1HTX-440-FLP-DM Duct Mount Humidity + Temperature Sensor cum Transmitter in FLP head
(SS Steam Size = 20 mm Dia. x 200 mm with 2 x 4-20mA output
3301-1
1.2HTX-440-FLP-DMDuct Mount Humidity + Temperature Sensor cum Transmitter in FLP head
(SS Steam Size = 20 mm Dia. x 200 mm with 2 x 0-10V output
3301-2
1.3HTX-440-FLP-DM Duct Mount Humidity + Temperature Sensor cum Transmitter in FLP head
(SS Steam Size = 20 mm Dia. x 200 mm with 2 x 0-1V output